Question Asked
Please confirm if the transformer will be placed under water ? Or what kind of environment will inside the vault?
Answer
The vaults are typically wet with some standing water. While we don’t plan for them being underwater, they should be quoted as being able to be submerged.
Question Asked
How many low voltage bushings do we need?
Answer
We will need 4 low voltage bushings for max configurability.